Wind evaporators are alternative evaporators for air source heat pumps which rely on wind-driven or natural convection to move air across the heat transfer surfaces. A fully automatic, computer-controlled test facility which allows side-by-side testing of wind evaporator and conventional heat pumps and monitoring of weather conditions has been designed and built at University College Galway. The aim of this paper is to quantify the advantages of wind evaporators by comparing the performance of a wind evaporator heat pump with that of a conventional heat pump over an extended testing period and by examining the relationship between weather conditions and heat pump performance. In this paper, results are presented in the form of plots of coefficient of performance (COP), compressor power, evaporator and condenser heat transfers and climatic variables against time. In addition, a testing period coefficient of performance has been calculated for each heat pump. The results show that wind speed is the dominant climatic variable affecting wind evaporator heat pump performance, and that frost growth does not significantly reduce this performance. Even at extremely low wind speeds, the COP of the wind evaporator heat pump is not significantly affected. After over 460 hr of testing, the testing period COP of the wind evaporator heat pump shows a 16 percent increase over that of the conventional heat pump. (Refer to Nomenclature in Part I of this paper.)
Skip Nav Destination
Article navigation
December 1992
Research Papers
Wind Evaporator Heat Pumps—Part II: Thermal Performance Results
J. M. O’Reilly,
J. M. O’Reilly
Thermal Engineering Research Unit (CATERU), University College Galway, Galway, Ireland
Search for other works by this author on:
P. F. Monaghan
P. F. Monaghan
Department of Mechanical Engineering, University College Galway, Galway, Ireland
Search for other works by this author on:
J. M. O’Reilly
Thermal Engineering Research Unit (CATERU), University College Galway, Galway, Ireland
P. F. Monaghan
Department of Mechanical Engineering, University College Galway, Galway, Ireland
J. Energy Resour. Technol. Dec 1992, 114(4): 286-290 (5 pages)
Published Online: December 1, 1992
Article history
Received:
October 30, 1990
Revised:
May 19, 1992
Online:
April 16, 2008
Citation
O’Reilly, J. M., and Monaghan, P. F. (December 1, 1992). "Wind Evaporator Heat Pumps—Part II: Thermal Performance Results." ASME. J. Energy Resour. Technol. December 1992; 114(4): 286–290. https://doi.org/10.1115/1.2905955
Download citation file:
10
Views
Get Email Alerts
Cited By
Related Articles
Wind Evaporator Heat Pumps—Part I: Test Methods
J. Energy Resour. Technol (December,1992)
Modeling of Surge Characteristics in Turbo Heat Pumps
J. Turbomach (October,2011)
Development of an Outdoor Test Facility for Wind Convectors
J. Sol. Energy Eng (November,1990)
Centrifugal Compressor Surge in Closed-Loop Systems: Initial Modeling and Comparison With Experiments
J. Eng. Gas Turbines Power (March,2025)
Related Proceedings Papers
Related Chapters
Analog Calculations of Heat Pump System with Flash-Tank in Scroll Compressor
International Conference on Computer Technology and Development, 3rd (ICCTD 2011)
Threshold Functions
Closed-Cycle Gas Turbines: Operating Experience and Future Potential
Outlook
Closed-Cycle Gas Turbines: Operating Experience and Future Potential